Categories

Photovoltaics surge protection T1+T2 DS 50 PVS

Characteristics
- Surge protector photovoltaic type 1+2
- Iimp = 5kA/pole (10/350
- internal disconnection, status indicator
- follow and operating current: none
- remote signaling

Follow current [IF]
0 kA  
Fault indication
mechanisch, Rot  
Material housing
Thermoplastik PEI UL-94-V0  
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Switching capacity signaling contact
250 V/0,5 A (AC) / - 30 V / 2 A (DC)  
Energetically coordinated protective effect to the terminal
Yes  
Exhausting
No  
Nominal voltage DC
1000 V  
Mounting method
DIN rail (top hat rail) 35 mm  
Construction size
3 modular spacing  
System configuration DC
Yes  
Integrated backup fuse
No  
Total discharge current (8/20) (L N-PE)
60 kA  
Degree of protection (IP)
IP20  
Test standards USA
UL 1449 ed.3  
Test standards Europe
EN 50539-11  
Test standards France
UTE C61-740-51  
   
Article No. E-Number SPD type Signaling contact max. discharge current (Imax) Operation voltage max. [Uc] Voltage protection level [Up] Impulse current [Iimp]_(10/350) Response time [ta] Nominal discharge surge current (8/20) VPE Quantity
   
Photovoltaics surge protection 296.480.393 808 486 330 T1 / T2 Yes 40 ≤1200VDC 2.6 5 0 15 1
Photovoltaics surge protection 296.482.393 808 486 340 T1 / T2 Yes 40 ≤1200VDC 2.6 6.25 0 15 1