Categories

Junction box PV GAK 410-MC4

Characteristics
Generator boxes with preassembled surge protection and grounding plate:

Legend
a) type 1+2 GAK + 60 VGPVS-1000-4ST-4MPP
b) type 1+2 GAK + 50 PVS-1000-4ST-4MPP
c) type 1+2 GAK + 50 VGPVS-1000-4ST-4MPP
d) type 2 GAK + 50 PV-1000-4ST-4MPP

Nominal line voltage Un DC
1000 V  
Follow current [IF]
0 kA  
Fault indication
mechanisch, Rot  
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Energetically coordinated protective effect to the terminal
Yes  
System configuration DC
Yes  
Integrated backup fuse
No  
Exhausting
No  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
degree of protection
IP65  
number of modules
20  
contract rail
DIN-Schiene  
String / MPP
4ST-4MPP  
inputs PG / MC4
MC 4  
outputs PG / MC4
MC 4  
Ground base plate
Yes  
Test standards USA
UL 1449 ed.3  
Test standards France
UTE C61-740-51  
   
Article No. E-Number SPD type Operation voltage max. [Uc] Impulse current [Iimp]_(10/350) max. discharge current (Imax) Nominal cross section conductor Voltage protection level [Up] Response time [ta] comment VPE Quantity
   
Junction box PVGAK+60VG-1000-4ST-4MPP MC4 296.050.254 969 112 064 T1 / T2 ≤1200VDC 12.5 40 6 - 35 2.8 ≤25 a) 1
Junction box PV GAK+ 50 PVS-1000-4ST-4MPP 296.050.854 969 112 174 T1 / T2 ≤1200VDC 6.25 40 2.5 - 25 2.6 ≤25 b) 1
Junction box PV GAK+50VG-1000-4ST-4MPP 296.050.454 969 111 834 T1 / T2 ≤1200VDC 6.25 40 2.5 - 25 2.8 ≤25 c) 1
Junction box PVGAK+50-1000-4ST-4MPP MC4 296.050.654 969 111 944 T2 ≤1200VDC 5 40 2.5 - 25 2.6 ≤25 d) 1