Categories
Article No. 291.410.223
E-Number 808 488 420
Technical specification
SPD type T2  
Number of poles 3  
Continuous voltage AC max. 275 V  
Nominal line voltage Un AC 230 V  
Nominal frequency [fn] 0 - 100 Hz  
TOV-voltage L-N [UT] 335 V / 5 sec.  
Operating current [Ic] 0 kA  
Follow current [IF] 0 kA  
follow current extinguishing capability [Ifi] Unendlich kA eff  
Nominal discharge surge current (8/20) 15 kA  
Discharge current max. (8/20) µs [Imax] 25 kA  
Total discharge current (8/20) (L N-PE) 75 kA  
max. discharge current (Imax) 25 kA  
Voltage protection level max. (by In) [Up] 1.25 kV  
Protection level max. (at Imax) 1.25 kV  
Voltage protection level [Up] 1.25 kV  
Response time [ta] <20 ns  
Short circuit resistance (Icw) 100 kA  
Integrated backup fuse Yes  
Signaling on the device Optic  
Nominal cross section conductor 2.5 - 25 mm²
Remote signalling Yes  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V/0,5 A (AC) / 30 V / 3 A (DC)  
Fault indication mechanisch, Rot  
Mounting on Hutschiene 35 mm  
Temperature range -40 - 85 °C
Construction size 3 modular spacing  
Mounting method DIN rail (top hat rail) 35 mm  
Degree of protection IP 20  
Degree of protection (IP) IP20  
Standards
Test standards Germany DIN EN 61643-11  
Test standards Europe DIN EN 61643-11  
Test standards International IEC 61643-11  
Test standards USA UL 1449 ed.4  
Test standards France DIN EN 61643-11  
Homologation KEMA / EAC  
Commercial specification
Customs number 85363000  
country of origin RC  
Logistic specification
VPE Weight 0.336 kg